How conduit fill is calculated
Add up the cross-sectional area of the conductors and compare it with the inside area of the raceway. The parts of NEC Chapter 9 that do the work:
- Table 1: the maximum fill, 53% for one conductor, 31% for two, 40% for three or more.
- Table 4: the inside area of each raceway type and trade size. ¾" EMT, ¾" PVC 40 and ¾" rigid are three different numbers.
- Table 5: the area of each insulated conductor by size and insulation. Bare conductors use Table 8.
- Notes 3, 4 and 7: grounding conductors count, a nipple of 24 in or less may be filled to 60%, and a same-size count rounds up at 0.8.
fill % = Σ conductor areas ÷ raceway area × 100
Worked examples
- How many 12 AWG THHN fit in ½" and ¾" EMT? 9 in ½" and 16 in ¾", the same counts as Annex C. With XHHW, ¾" EMT takes 11: the thicker insulation needs more room.
- Three 8 AWG THHN plus a 10 AWG THHN ground in ¾" EMT. The conductors total 0.1309 in² against 0.5330 in² of raceway: 24.6%, within the 40% limit.
- The nipple rule. Six 10 AWG THHN fill ½" EMT to 41.6%. As a run that's over the 40% limit; as a nipple of 24 in or less the limit is 60%, so it's allowed. It only helps on short connections between enclosures, such as a panel to a wireway.
More of these, with a table by wire size: How many 12 gauge wires in 3/4 conduit?
Common mistakes
- Leaving out the equipment grounding conductor (Note 3).
- Using EMT areas for PVC. At the common trade sizes, Schedule 40 and 80 PVC are smaller inside than EMT.
- Stopping at fill. A ¾" EMT that legally holds 16 current-carrying 12s has to derate them under 310.15(C)(1); check that with the Wire Size calculator.