Two different ground wires
Equipment grounding conductor (EGC)
Table 250.122 sizes the EGC by the rating of the overcurrent device ahead of the circuit, using the first row whose "not exceeding" value covers it. A 20 A circuit gets 12 AWG copper; a 60 A circuit 10 AWG; a 200 A feeder 6 AWG copper or 4 AWG aluminum.
Grounding electrode conductor (GEC)
Table 250.66 sizes the GEC by the largest ungrounded service-entrance conductor. A 200 A dwelling service on 4/0 aluminum (the size 310.12's 83% rule lands on) needs a 4 AWG copper GEC (2 AWG aluminum); on 2/0 copper, 4 AWG copper. Those are the figures for the conductor to a water pipe; the run to the rods can stop at 6 AWG copper (250.66(A)).
Worked example: upsizing the EGC (250.122(B))
A 100 A feeder needs 3 AWG copper for ampacity, but it's pulled in 1 AWG to control voltage drop. Table 250.122 gives an 8 AWG copper EGC for 100 A. The phase conductors grew from 52,620 to 83,690 circular mils, a ratio of 1.590. The EGC must grow by the same ratio, and the next standard size that's large enough is 4 AWG copper (4 AWG aluminum).
Not sure the phase conductors were upsized? Find the size ampacity alone requires with the Wire Size calculator; if you're installing something bigger, 250.122(B) applies.
Common mistakes
- Sizing the EGC from the conductor size instead of the breaker size.
- Using Table 250.66 for an equipment ground, or Table 250.122 for an electrode conductor.
- Upsizing the hots for voltage drop and leaving the EGC at the table minimum.
- Splitting one EGC between parallel raceways instead of a full-size EGC in each (250.122(F)).
This page cites the code but doesn't reproduce NEC text or tables. Use your copy of the NEC 2023 for the exact wording.