Box Fill Calculator

Count the conductors, clamps, devices and grounds in a box, then check the required volume against a standard box or the volume marked on yours.

Required volume FITS
12.00in³
Box
18.0 in³
Fill
67%
Largest
14 AWG

NEC 314.16(B) · NEC 2023

Values checked against the printed NEC 2023 tables, using the same engine as the Voltkit app.

Show calculation
  1. Conductors3 × 14 AWG (Table 314.16(B))6.00 in³
  2. Device yokes · 14 AWG1 × 2 × 2.00 (wire on device)4.00 in³
  3. Equipment grounds1 × 2.00 (up to 4 EGCs)2.00 in³
  4. Required volumesum of allowances12.00 in³
  5. Box volumeDevice 3×2, 3½" deep (Table 314.16(A))18.00 in³
  6. ResultBox is large enoughOK

NEC 314.16(A) & (B)

Box

Conductors

Count each insulated conductor that starts or ends in the box, and each one passing through. Pigtails and wires that never leave the box don't count.

Devices

Each yoke counts double, at the largest wire connected to the device on it (314.16(B)(4)), not the largest in the box. A size that isn't in the box is counted at the largest one.

Fittings

Internal cable clamps
Luminaire stud / hickey (one per type)

Equipment ground

Grounding conductors present

Count grounds and bonding jumpers. Up to four count once, at the largest; each one beyond four adds a quarter (314.16(B)(5)).

Use it offline on the job — get Voltkit

This calculator and the rest of Voltkit run on your phone with no signal: basements, rooftops, rural sites. Every result shows its worked steps and code section.

How box fill is calculated

NEC 314.16(B) turns everything in the box into a number of "allowances", and each allowance is the Table 314.16(B) volume for one conductor (2.00 in³ for 14 AWG, 2.25 in³ for 12 AWG, on up to 6 AWG).

  • Conductors (B)(1): one each for every conductor that comes into the box, at its own size. Pigtails count zero.
  • Internal cable clamps (B)(2): one allowance for all of them, at the largest conductor.
  • Support fittings (B)(3): one allowance for each type of fitting (fixture studs, hickeys), at the largest conductor. Two studs still count once.
  • Devices (B)(4): two allowances per yoke, at the largest conductor connected to that device.
  • Equipment grounds (B)(5): one allowance for up to four, plus a quarter for each one after that, at the largest EGC. Enter how many enter the box and the calculator adds the quarters.

required in³ = Σ (allowances × volume per allowance) ≤ box in³

Worked examples

  1. How many 14 AWG in a 4" square, 1½" deep box? Its Table 314.16(A) volume is 21.0 in³, enough for 10 14 AWG or 9 12 AWG with nothing else in the box. Clamps, a device and the grounds all come out of that count.
  2. A receptacle on 12/2 NM, in and out, in a 3 × 2 × 3½" device box (18.0 in³) with internal clamps. Four insulated 12 AWG are 9.00 in³, the clamps 2.25 in³, the receptacle 4.50 in³ and both grounds together 2.25 in³. Total 18.00 in³, so the box is large enough, and that's the deepest standard 3 × 2 there is.

Step by step, with the smallest box for a switch loop: How to calculate box fill.

Common mistakes

  • Counting each ground separately, or leaving them out. Up to four count once; it's the fifth and later that add a quarter each.
  • Counting the device as one allowance.
  • Looking up a plastic box in the metal-box table.

Worked examples on this page are computed by the same engine as the Voltkit app. The page cites NEC 2023 sections but doesn't reproduce NFPA text or tables; use your copy of the code for the exact wording.

Worked examples

Frequently asked questions

Can I use Table 314.16(A) for a plastic box?

No. Table 314.16(A) lists metal boxes. Nonmetallic boxes, and other boxes of 100 in³ or less that aren't in the table, must be marked with their volume by the manufacturer (314.16(A)(2)), so use the number molded or printed inside the box and enter it as your own volume.

Do wire nuts and pigtails count?

No. Wire connectors aren't counted, and a conductor that starts and ends inside the box, such as a pigtail, doesn't count either. A cable connector counts only if its clamping part is inside the box; then it's the internal-clamp allowance.

Does a plaster ring or extension ring add volume?

Yes, if it is marked with its volume or is made from a box listed in Table 314.16(A) (314.16(A)). Add the marked figure to the box volume. An unmarked ring adds nothing.

Which wire size does a device count at?

The largest conductor connected to that device (314.16(B)(4)), not the largest in the box. A switch on 14 AWG in a box that also carries 12 AWG counts at 14: 4.00 in³ instead of 4.50 in³. Enter one device row per wire size; a size that isn't in the box is counted at the largest one present.

What about conductors bigger than 6 AWG?

Table 314.16(B) stops at 6 AWG. For 4 AWG and larger, the box is sized from the raceway trade sizes under 314.28 instead. Use the Pull Box calculator for that.