How pull boxes are sized
NEC 314.28(A) sizes a pull or junction box from the trade sizes of the raceways, not from the conductors' volume:
- Straight pull (A)(1): length at least 8 × the largest raceway trade size.
- Angle or U pull (A)(2): from each entry to the opposite wall, at least 6 × the largest raceway plus the other raceways in the same row on that wall.
- Entry spacing (A)(2): raceways enclosing the same conductor at least 6 × the larger raceway apart.
The box has to work in every direction a conductor is pulled, so check each wall with entries on it. If any dimension of the box is over 6 ft, 314.28(B) also requires the conductors inside to be cabled or racked.
Worked examples
- Straight pull with 2" conduit. The box must be at least 16 in long.
- Angle pull: a 3" conduit and two 2" conduits on the same wall. 6 × 3" plus 2" + 2" gives 22 in to the opposite wall (it would be 18 in with the 3" alone). Entries carrying the same conductors must be at least 18 in apart.
This page cites the code but doesn't reproduce NEC text or tables. Use your copy of the NEC 2023 for the exact wording.